Technical Specifications
Electrical
Resolution of the analogue inputs
|
15 Bit
|
Input, current
|
Yes
|
Input, voltage
|
Yes
|
Input, resistor
|
No
|
Input, resistance thermometer
|
No
|
Input, thermocouple
|
No
|
Input signal, configurable
|
Yes
|
Output, current
|
No
|
Output, voltage
|
No
|
Output signal configurable
|
No
|
Analogue inputs configurable
|
Yes
|
Analogue outputs configurable
|
No
|
Type of electric connection
|
Screw connection
|
Fast transient burst
|
IEC1000-4-4: 2kV, 5 kHz
|
Conducted immunity
|
10V, 0.15...80 MHz
|
Radiated immunity
|
IEC1000-4-3: 10 V/m, 80...1,000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
|
Surge immunity
|
IEC1000-4-5: 1kV galvanic gun
|
Module power LED
|
On: indicates power is applied
|
Environmental
Operating temperature
|
-20 °C
|
ESD immunity
|
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
|
Operating altitude
|
2000 m
|
Storage temperature
|
-40 °C
|
Operating humidity
|
5...95% noncondensing
|
Input Specifications
Common mode voltage range
|
-27 to 27V
|
A/D converter type
|
Successive approximation
|
Number of inputs
|
4 differential (bipolar)
|
Common mode rejection
|
>55 dB at 50 and 60 Hz
|
Input update time
|
Typical: 130, 250, 290, 450, 530 ms (selectable)
|
Input impedance
|
Voltage Terminal: 200 KΩ
|
Current input protection
|
-32 mA
|
Voltage input protection
|
-30 V
|
Channel diagnostics
|
Over or under range or open circuit condition by bit reporting for analog inputs
|
General Specifications
Analog normal operating range
|
Voltage: -10...10V DC
|
Bus current draw, max
|
40 mA @ 5V DC, 50 mA @ 24V DC
|
Full scale analog ranges
|
Voltage: -10.5...10.5V DC, Current: -21...21 mA
|
Repeatability
|
-0.12 to 0.12%
|
Input and output group to system isolation
|
30V AC/30V DC rated working voltage (N.E.C. Class 2 required) (IEC Class 2 reinforced insulation) type test: 500V AC or 707V DC for 1 minute
|
Construction
Height
|
90 mm
|
Width
|
40 mm
|
Depth
|
87 mm
|
Recommended cable
|
Belden 8761 (shielded), (For 1762-IT4, shielded thermocouple extension wire for the specific type of thermocouple you are using. Follow thermocouple manufacturer’s recommendations.)
|
Output Specifications
Non-linearity
|
±0.12% (in percent full scale)
|
Typical overall accuracy
|
±0.32% full scale @ -20...65 °C, ±0.24% full scale @ 25 °C
|
Mechanical
Weight
|
Shipping: 240 g (0.53 lbs.) approximately (with cartoon)
|
Vibration
|
Operating: 5 g @ 10...500 Hz, 0.030 in. max. peak-to-peak
|
Shock
|
Operating: 30 g
|
Common Specifications
Hazardous environment class
|
Hazardous Location, Class I, Division 2 Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
|
Radiated and conducted emissions
|
EN50081-2: Class A
|
|
|
|